Marlew

Clad series MA-F

600 Volt
Cu 16 up to 10 AWG
Double insulation
ICEA S 73-532

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It counts with additional electromagnetic and mechanical protection.

Features

  • Temperature rating: 90ºC (operating), 160°C (short circuit)

  • Voltage rating: 600V AC

  • Construction requirements: As per ICEA S 73-532

  • Conductor requirements: As per ASTM B174

  • Conductor: Annealed electrolytic copper; flexible

  • Primary insulation: Special PVC

  • Secondary insulation: Nylon

  • Shield: Aluminium/polyester tape helical wrap with 100% coverage and overlap. Drain wire in contact with the aluminium side of the tape. Drain consists of a 7-wire tinned copper thread

  • Inner sheath: PVC

  • Armour: Double galvanized steel helical tape

  • Sheath: PVC fire-retardant; sunlight and mineral-oil resistant.

  • Fire requirements: As per ICEA T 30-520

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

Electromagnetic interference protection

Electromagnetic interference protection

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Direct burial

Direct burial

Identification

Standard
Sheath Conductors
MulticonductorMethod 3 Table E-2

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C. (Ohm/km) Electrical resistance at 90°C in C.A. at 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x
1613.9917.841814.412.6998.1
148.7711.18252017.512.512.511.3
125.527.04302421151513.5
103.484.44403228202018

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable formation N° Cond. x gauge AWG Diameter under armour mm External diameter mm Weight kg/km Code Mat Number Previous Code
7 x 161014.1331MA-F 7x16820053070MA 0716 FNe
10 x 1612.316.4424MA-F 10x16820053080MA 1016 FNe
12 x 1612.716.7462MA-F 12x16820053090MA 1216 FNe
14 x 1614.318.4547MA-F 14x16820053100MA 1416 FNe
16 x 161519.1593MA-F 16X16-MA 1616 FNe
19 x 1615.819.9658MA-F 19x16820053110MA 1916 FNe
21 x 1616.620.7707MA-F 21X16-MA 2116 FNe
24 x 161822.1785MA-F 24x16820053120MA 2416 FNe
27 x 1618.422.5841MA-F 27X16-MA 2716 FNe
30 x 1619.323.4907MA-F 30x16820053130MA 3016 FNe
32 x 162024.1954MA-F 32X16-MA 3216 FNe
37 x 1620.824.91052MA-F 37X16-MA 3716 FNe
48 x 1624.428.51351MA-F 48X16-MA 4816 FNe
4 x 141014.1324MA-F 4x14820053140MA 0414 FNe
5 x 1410.214.3341MA-F 5x14820053150MA 0514 FNe
7 x 141115.1405MA-F 7x14820053160MA 0714 FNe
10 x 1414.318.4561MA-F 10x14820053170MA 1014 FNe
12 x 1414.818.9617MA-F 12x14820053180MA 1214 FNe
14 x 1415.819.9686MA-F 14x14820053190MA 1414 FNe
16 x 1416.620.7750MA-F 16X14-MA 1614 FNe
19 x 1417.421.5840MA-F 19x14820053200MA 1914 FNe
21 x 1418.422.5908MA-F 21X14-MA 2114 FNe
24 x 142024.11013MA-F 24x14820053210MA 2414 FNe
27 x 1420.424.51092MA-F 27X14-MA 2714 FNe
30 x 1422.526.61250MA-F 30x14820053220MA 3014 FNe
32 x 1423.327.41316MA-F 32X14-MA 3214 FNe
37 x 1424.128.21457MA-F 37X14-MA 3714 FNe
48 x 1427.131.21788MA-F 48X14-MA 4814 FNe
3 x 121014.1331MA-F 3x12820053230MA 0312 FNe
4 x 1210.514.6371MA-F 4x12820053240MA 0412 FNe
5 x 1211.415.5424MA-F 5x12820053250MA 0512 FNe
7 x 1212.416.5514MA-F 7x12820053260MA 0712 FNe
10 x 1216.220.3717MA-F 10x12820053270MA 1012 FNe
12 x 1216.720.7797MA-F 12x12820053280MA 1212 FNe
14 x 1217.821.9892MA-F 14x12820053290MA 1412 FNe
16 x 1218.822.9983MA-F 16X12-MA 1612 FNe
19 x 1219.823.91112MA-F 19x12820053300MA 1912 FNe
21 x 1221.9261269MA-F 21X12-MA 2112 FNe
24 x 1223.827.91420MA-F 24x12820053310MA 2412 FNe
27 x 1224.328.41536MA-F 27X12-MA 2712 FNe
30 x 1225.529.61669MA-F 30x12820053320MA 3012 FNe
32 x 1226.430.51762MA-F 32X12-MA 3212 FNe
37 x 1227.431.51967MA-F 37X12-MA 3712 FNe
48 x 1230.936.22786MA-F 48X12-MA 4812 FNe
2 x 1010.915351MA-F 2x10820053330MA 0210 FNe
3 x 1011.515.6419MA-F 3x10820053340MA 0310 FNe
4 x 1012.616.7497MA-F 4x10820053350MA 0410 FNe
5 x 1014.618.7612MA-F 5x10820053360MA 0510 FNe
7 x 1015.819.9752MA-F 7x10820053370MA 0710 FNe
10 x 1019.623.71002MA-F 10x10820053380MA 1010 FNe
12 x 1020.224.31127MA-F 12x10820053390MA 1210 FNe
14 x 1022.726.81336MA-F 14x10820053400MA 1410 FNe
16 x 1023.9281477MA-F 16X10-MA 1610 FNe
19 x 1025.229.31680MA-F 19x10820053410MA 1910 FNe
21 x 1026.630.61825MA-F 21X10-MA 2110 FNe
24 x 1028.934.22379MA-F 24x10820053420MA 2410 FNe
27 x 1029.634.92570MA-F 27X10-MA 2710 FNe
30 x 1031.136.42791MA-F 30x10820053430MA 3010 FNe
32 x 1032.337.62945MA-F 32X10-MA 3210 FNe
37 x 1033.538.83278MA-F 37X10-MA 3710 FNe
48 x 1037.9444125MA-F 48X10-MA 4810 FNe