Clad series GF-H

Corrugated copper shielding + Steel wire armour

0.6/1kV
Flexible Cu 1 up to 4mm²
Up to 48 Conductors
Electromagnetic protection

Control, signalling, measuring and protective equipment, electric controls of high voltage substations (SSEE), its shielding allows adequate filtering of electromagnetic interference at frequencies up to 1 MHz. Installed in aerial trays, gutters or conduits, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature rating: 70ºC (operating), 160°C (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 2178-1 – IEC 60502-1

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: PVC

  • Bedding: PVC

  • Shield: Corrugated copper tape longitudinal overlapping wrap

  • Inner sheath: PVC

  • Armour: Galvanized steel wire armour

  • Sheath: PVC, fire-retardant

  • Fire requirements: As per IEC 60332-3-24

  • EMC requirements: Transfer impedance lower than 2 ohm/km up to 1MHz (as per IRAM 63020; HN 33-S-34)

Corrugated copper shield

Corrugated copper shield

Fire-retardant

Fire-retardant

Flexible stranded conductors

Flexible stranded conductors

Sequentially marked

Sequentially marked

Industrial applications

Industrial applications

Tray cable

Tray cable

Identification

Standard
Sheath Conductors
Multiconductors with alpha-numerically

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Nominal cross-section sq mm² Electrical resistance at 20°C in C.C. Ohm/km Electrical resistance at 70°C in C.A. Ohm/km Current-carrying capacity in free air. At 40°C as per IEC 364-5-523. Formations in perforated trays or ladder type. (Ampere)
2x 4x 7x 10x 19x 30x 48x
119.523.3--------------
1.513.315.918.115.312.79.19.18.16.3
2.57.989.55252117.512.512.511.38.8
44.955.92332923.116.516.514.9--

As from seven-conductors, we’ve additionally applied the correction factor for more than three conductors the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable formation N° Cond. x cross-section (mm²) Diameter under armour mm External diameter mm Weight kg/km Code
2x114.619.2658GF 0210 H
3x114.619.2663GF 0310 H
4x114.620.1803GF 0410 H
5x115.120.6837GF 0510 H
7x116.121.6921GF 0710 H
10x118.123.61039GF 1010 H
12x119.125.31258GF 1210 H
14x120.126.31347GF 1410 H
19x122.128.31519GF 1910 H
24x124.130.31717GF 2410 H
30x125.6321885GF 3010 H
37x128.134.52155GF 3710 H
48x130.638.52773GF 4810 H
2x1.514.619.2664GF 0215 H
3x1.514.620.1808GF 0315 H
4x1.515.120.6843GF 0415 H
5x1.516.121.6922GF 0515 H
7x1.517.122.61004GF 0715 H
10x1.519.125.31276GF 1015 H
12x1.520.126.31369GF 1215 H
14x1.521.127.31450GF 1415 H
19x1.523.629.81700GF 1915 H
24x1.525.6321914GF 2415 H
30x1.527.6342156GF 3015 H
37x1.529.636.22406GF 3715 H
48x1.533.641.53339GF 4815 H
2x2.514.620.1812GF 0225 H
3x2.515.120.6855GF 0325 H
4x2.516.121.6937GF 0425 H
5x2.517.122.61014GF 0525 H
7x2.518.123.61110GF 0725 H
10x2.520.626.81451GF 1025 H
12x2.522.128.31587GF 1225 H
14x2.523.129.31697GF 1425 H
19x2.525.631.81969GF 1925 H
24x2.528.134.72301GF 2425 H
30x2.530.137.82881GF 3025 H
37x2.533.641.53466GF 3725 H
48x2.536.644.73958GF 4825 H
2x416.622.1962GF 0240 H
3x417.623.11049GF 0340 H
4x418.624.11134GF 0440 H
5x419.625.81378GF 0540 H
7x421.127.31540GF 0740 H
10x424.130.51828GF 1040 H
12x425.6321990GF 1240 H
14x427.133.52173GF 1440 H
19x430.638.32930GF 1940 H
24x433.641.73505GF 2440 H
30x436.644.73974GF 3040 H
37x440.648.94811GF 3740 H