Clad series GF-F

0.6/1kV
Flexible Cu 1 up to 4mm²
Up to 48 Conductors
Electromagnetic protection

Control, signalling, measuring and protective equipment, electric controls of high voltage substations (SSEE), its shielding allows adequate filtering of electromagnetic interference at frequencies up to 1 MHz. Installed in aerial trays, gutters or conduits, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature rating: 70ºC (operating), 160°C (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 2178-1 – IEC 60502-1

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: PVC

  • Bedding: PVC

  • Shield: Corrugated copper tape longitudinal overlapping wrap

  • Inner sheath: PVC

  • Armour: Double galvanized steel helical tape

  • Sheath: PVC, fire-retardant

  • Fire requirements: As per IEC 60332-3-24

  • EMC requirements: Transfer impedance lower than 2 ohm/km up to 1MHz (as per IRAM 63020; HN 33-S-34)

Corrugated copper shield

Corrugated copper shield

Fire-retardant

Fire-retardant

Flexible stranded conductors

Flexible stranded conductors

Sequentially marked

Sequentially marked

Industrial applications

Industrial applications

Tray cable

Tray cable

Identification

Standard
Sheath Conductors
Multiconductors with alpha-numerically

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Nominal cross-section sq mm² Electrical resistance at 20°C in C.C. Ohm/km Electrical resistance at 70°C in C.A. Ohm/km Current-carrying capacity in free air. At 40°C as per IEC 364-5-523. Formations in perforated trays or ladder type. (Ampere)
2x 4x 7x 10x 19x 30x 48x
119.523.3--------------
1.513.315.918.115.312.79.19.18.16.3
2.57.989.55252117.512.512.511.38.8
44.955.92332923.116.516.514.9--

As from seven-conductors, we’ve additionally applied the correction factor for more than three conductors the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable formation N° Cond. x cross-section (mm²) Diameter under armour mm External diameter mm Weight kg/km Code Mat Number
10x118.121.9726GF-F 10x1820012060
12x119.122.9786GF-F 12x1820012070
14x120.123.9849GF-F 14x1820012080
19x122.125.9986GF-F 19x1820012090
24x124.127.91132GF-F 24x1820012100
30x125.629.41264GF-F 30x1820012110
37x128.131.91469GF-F 37x1820012120
48x130.634.61730GF-F 48x1820012130
5x1.516.119.9634GF-F 5x1.5820012170
7x1.517.120.9703GF-F 7x1.5820012180
10x1.519.122.9804GF-F 10x1.5820012190
12x1.520.123.9871GF-F 12x1.5820012200
14x1.521.124.9943GF-F 14x1.5820012210
19x1.523.627.41129GF-F 19x1.5820012220
24x1.525.629.41293GF-F 24x1.5820012230
30x1.527.631.41482GF-F 30x1.5820012240
37x1.529.633.61696GF-F 37x1.5820012250
48x1.533.637.82136GF-F 48x1.5820012260
3x2.515.118.9591GF-F 3x2.5820012280
4x2.516.119.9650GF-F 4x2.5820012290
5x2.517.120.9714GF-F 5x2.5820012300
7x2.518.121.9797GF-F 7x2.5820012310
10x2.520.624.4940GF-F 10x2.5820012320
12x2.522.125.91054GF-F 12x2.5820012330
14x2.523.126.91139GF-F 14x2.5820012340
19x2.525.629.41362GF-F 19x2.5820012350
24x2.528.132.11613GF-F 24x2.5820012360
30x2.530.134.11851GF-F 30x2.5820012370
37x2.533.637.82263GF-F 37x2.5820012380
48x2.536.642.43103GF-F 48x2.5820012390
2x416.620.4668GF-F 2x4820012400
3x417.621.4742GF-F 3x4820012410
4x418.622.4814GF-F 4x4820012420
5x419.623.4893GF-F 5x4820012430
7x421.124.91033GF-F 7x4820012440
10x424.127.91230GF-F 10x4820012450
12x425.629.41369GF-F 12x4820012460
14x427.130.91512GF-F 14x4820012470
19x430.634.61904GF-F 19x4820012480
24x433.6382300GF-F 24x4820012490
30x436.642.43119GF-F 30x4820012500
37x440.646.63873GF-F 37x4820012510