series G GC

Reelable flexible cables for mining use

2000 Volt
Cu 6 AWG up to 500 MCM
EPR/TPU
Extra-Heavy Duty

This type of cable is required for extra-heavy duty industrial use. Designed for applications such as longwall shearers, continuous miners, loaders, drills, conveyors, pumps and mobile equipment; both in open pit mining and underground mines and similar applications. Suitable for applications where grounding conductors (G) and ground check conductors (GC) are needed

Features

  • Temperature rating: 90°C (operating), 130°C (overload), 250°C (short circuit)

  • Voltage rating: 2000V AC

  • Construction requirements: As per ICEA S 75-381

  • Conductor requirements: As per ASTM B 172/173/174

  • Conductor: Annealed electrolytic copper - Flexible stranding class

  • Insulation: EPR

  • Cable assembly: 3 phases + 2 G (Ground) + 1 GC (Ground Check)

  • Sheath: Double Polyurethane protection UV and chemicals resistant; with internal textile braid reinforcement

  • Fire requirements: As per UL 2556 (FT1)

  • Outdoors requirements: As per UL 2556 (UV rays)

Flame retardant

Flame retardant

Flexible stranded conductors

Flexible stranded conductors

High sliding

High sliding

UV resistant

UV resistant

Tear and impacts

Tear and impacts

Harsh environment

Harsh environment

Identification

Standard
Sheath Conductors Grounding conductor Ground Check conductor
3 ConductorsBare copper

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of colour armour.

ELECTRICAL CHARACTERISTICS, DIMENSIONS & WEIGHT

Phase conductors size AWG / MCM Protection conductor size AWG/MCM Ground Check conductor size AWG Electrical resistance at 20ºC (*) in C.C. ohm/km Current-carrying capacity in free air (**) (Ampere) External diameter mm Weight kg/km Radio de curvatura mm Pulling tension daN Code
610101,427926,7958160,256G-GC 0306 2kV
48100,8910430,11348180,685G-GC 0304 2kV
38100,71312031,81532190,8102G-GC 0303 2kV
27100,56613834,11843204,6127G-GC 0302 2kV
1680,44816138,42331230,4162G-GC 0301 2kV
1/0580,35518641,92782251,4202G-GC 31/0 2kV
2/0480,28421544,53300267253G-GC 32/0 2kV
3/0380,22624948,13982288,6317G-GC 33/0 2kV
4/0280,17928751,84815310,8397G-GC 34/0 2kV
250280,15232060,86056364,8457G-GC 3250 2kV
300180,12635765,17049390,6549G-GC 3300 2kV
3501/080,10839468,18067408,6646G-GC 3350 2kV
5002/080,07648777,110693462,6902G-GC 3500 2kV

(*) Informed Electrical resistance refers to phase conductors only. (**) ICEA S 75-381 H-1 Chart, maximum operating temperature 90ºC and 40ºC ambient temperature.