Clad series FX-H

Steel wire armour

0.6/1kV
Flexible Cu 1 up to 4mm²
Up to 48 Conductors
XLPE 90°C / PVC

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature rating: 90ºC (operating),130ºC (overload) and 250ºC (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 2178-1 – IEC 60502-1

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Cross-linked polyethylene)

  • Bedding: PVC

  • Armour: Galvanized steel wire armour

  • Sheath: PVC, fire-retardant; sunlight and oils resistant

  • Fire requirements: As per IEC 60332-1

  • Oils requirements: As per ICEA S 73-532

  • Outdoor requirements: As per UL 2556 (UV rays)

Flame retardant

Flame retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Tray cable

Tray cable

Direct burial

Direct burial

Identification

Standard
Sheath Conductors
Multiconductors alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Nominal cross-section sq mm² Electrical resistance at 20ºC in C.C Ohm/km Electrical resistance at 90ºC in C.A. Ohm/km Current-carrying capacity in free air. At 40°C as per IEC 364-5-523. Formations in perforated trays or ladder type. (Ampere)
2x 4x 7x 10x 19x 30x 48x
119.524.86--------------
1.513.316.96232016.111.511.510.48.1
2.57.9810.18312821.715.515.514.010.9
44.956.31433630.121.521.519.4--

As from seven-conductors, we’ve additionally applied the correction factor for more than three conductors the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x cross-section (mm²) Diameter under armour mm External diameter mm Weight kg/km Code
2x17.211.8254FX 0210 H
3x17.612.2272FX 0310 H
4x18.312.9303FX 0410 H
5x19.013.6334FX 0510 H
7x19.814.4377FX 0710 H
10x111.617.1557FX 1010 H
12x112.518.0611FX 1210 H
14x113.318.8664FX 1410 H
19x115.220.7795FX 1910 H
24x116.823.01033FX 2410 H
30x118.624.81185FX 3010 H
37x120.426.61338FX 3710 H
48x122.929.31592FX 4810 H
2x1.57.712.3281FX 0215 H
3x1.58.212.8302FX 0315 H
4x1.58.913.5339FX 0415 H
5x1.59.714.3380FX 0515 H
7x1.510.615.2432FX 0715 H
10x1.512.518.0642FX 1015 H
12x1.513.519.0705FX 1215 H
14x1.514.419.9769FX 1415 H
19x1.516.522.0913FX 1915 H
24x1.518.324.51188FX 2415 H
30x1.520.226.41385FX 3015 H
37x1.522.228.41571FX 3715 H
48x1.525.031.41877FX 4815 H
2x2.58.613.2327FX 0225 H
3x2.59.113.7357FX 0325 H
4x2.510.014.6403FX 0425 H
5x2.510.915.5460FX 0525 H
7x2.511.917.4647FX 0725 H
10x2.514.119.6778FX 1025 H
12x2.515.320.8872FX 1225 H
14x2.516.321.8954FX 1425 H
19x2.518.724.91296FX 1925 H
24x2.520.726.91510FX 2425 H
30x2.522.929.31777FX 3025 H
37x2.525.331.72046FX 3725 H
48x2.528.936.82807FX 4825 H
2x49.714.3387FX 0240 H
3x410.314.9438FX 0340 H
4x411.315.9499FX 0440 H
5x412.317.8691FX 0540 H
7x413.519.0807FX 0740 H
10x416.022.21108FX 1040 H
12x417.423.61234FX 1240 H
14x418.624.81357FX 1440 H
19x421.327.51663FX 1940 H
24x423.730.11963FX 2440 H
30x426.332.92332FX 3040 H
37x429.403237.30323062FX 3740 H