Clad series FX-F

Steel tape armour

0.6/1kV
Flexible Cu 1 up to 4mm²
Up to 48 Conductors
XLPE 90°C / PVC

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature rating: 90ºC (operating),130ºC (overload) and 250ºC (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 2178-1 – IEC 60502-1

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Cross-linked polyethylene)

  • Bedding: PVC

  • Armour: Double galvanized steel helical tape

  • Sheath: PVC, fire-retardant; sunlight and oils resistant

  • Fire requirements: As per IEC 60332-1

  • Oils requirements: As per ICEA S 73-532

  • Outdoor requirements: As per UL 2556 (UV rays)

Flame retardant

Flame retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Tray cable

Tray cable

Direct burial

Direct burial

Identification

Standard
Sheath Conductors
Multiconductors alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Nominal cross-section sq mm² Electrical resistance at 20ºC in C.C Ohm/km Electrical resistance at 90ºC in C.A. Ohm/km Current-carrying capacity in free air. At 40°C as per IEC 364-5-523. Formations in perforated trays or ladder type. (Ampere)
2x 4x 7x 10x 19x 30x 48x
119.524.86--------------
1.513.316.96232016.111.511.510.48.1
2.57.9810.18312821.715.515.514.010.9
44.956.31433630.121.521.519.4--

As from seven-conductors, we’ve additionally applied the correction factor for more than three conductors the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x cross-section (mm²) Diameter under armour mm External diameter mm Weight kg/km Code
10x111.615.4347FX 1010 F
12x112.516.3388FX 1210 F
14x113.317.1427FX 1410 F
19x115.219.0521FX 1910 F
24x116.820.6610FX 2410 F
30x118.622.4725FX 3010 F
37x120.424.2843FX 3710 F
48x122.926.71019FX 4810 F
5x1.510.013.8303FX 0515 F
7x1.510.614.4339FX 0715 F
10x1.512.516.3409FX 1015 F
12x1.513.517.3460FX 1215 F
14x1.514.418.2510FX 1415 F
19x1.516.520.3628FX 1915 F
24x1.518.322.1743FX 2415 F
30x1.520.224.0888FX 3015 F
37x1.522.226.01039FX 3715 F
48x1.525.029.01282FX 4815 F
3x2.510.013.8310FX 0325 F
4x2.510.013.8318FX 0425 F
5x2.510.914.7365FX 0525 F
7x2.511.915.7430FX 0725 F
10x2.514.117.9527FX 1025 F
12x2.515.319.1598FX 1225 F
14x2.516.320.1668FX 1425 F
19x2.518.722.5837FX 1925 F
24x2.520.724.51000FX 2425 F
30x2.522.926.71204FX 3025 F
37x2.525.329.11423FX 3725 F
48x2.528.933.11819FX 4825 F
2x410.013.8317FX 0240 F
3x410.314.1346FX 0340 F
4x411.315.1402FX 0440 F
5x412.316.1467FX 0540 F
7x413.517.3561FX 0740 F
10x416.019.8696FX 1040 F
12x417.421.2799FX 1240 F
14x418.622.4898FX 1440 F
19x421.325.11141FX 1940 F
24x423.727.51379FX 2440 F
30x426.330.31682FX 3040 F
37x429.433.62052FX 3740 F