Marlew

Clad series FX-F

0.6/1kV
Flexible Cu 1 up to 4mm²
Up to 48 Conductors
XLPE 90°C / PVC

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature rating: 90ºC (operating),130ºC (overload) and 250ºC (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 2178-1 – IEC 60502-1

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Cross-linked polyethylene)

  • Bedding: PVC

  • Armour: Double galvanized steel helical tape

  • Sheath: PVC, fire-retardant; sunlight and oils resistant

  • Fire requirements: As per IEC 60332-1

  • Oils requirements: As per ICEA S 73-532

  • Outdoor requirements: As per UL 2556 (UV rays)

Flame retardant

Flame retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Tray cable

Tray cable

Direct burial

Direct burial

Identification

Standard
Sheath Conductors
Multiconductors alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Nominal cross-section sq mm² Electrical resistance at 20ºC in C.C Ohm/km Electrical resistance at 90ºC in C.A. Ohm/km Current-carrying capacity in free air. At 40°C as per IEC 364-5-523. Formations in perforated trays or ladder type. (Ampere)
2x 4x 7x 10x 19x 30x 48x
119.524.86--------------
1.513.316.96232016.111.511.510.48.1
2.57.9810.18312821.715.515.514.010.9
44.956.31433630.121.521.519.4--

As from seven-conductors, we’ve additionally applied the correction factor for more than three conductors the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x cross-section (mm²) Diameter under armour mm External diameter mm Weight kg/km Code Mat Number
10x111.615.4347FX-F 10x1820002060
12x112.516.3388FX-F 12x1820002070
14x113.317.1427FX-F 14x1820002080
19x115.219.0521FX-F 19x1820002090
24x116.820.6610FX-F 24x1820002100
30x118.622.4725FX-F 30x1820002110
37x120.424.2843FX-F 37x1820002120
48x122.926.71019FX-F 48x1820002130
5x1.510.013.8303FX-F 5x1.5820002170
7x1.510.614.4339FX-F 7x1.5820002180
10x1.512.516.3409FX-F 10x1.5820002190
12x1.513.517.3460FX-F 12x1.5820002200
14x1.514.418.2510FX-F 14x1.5820002210
19x1.516.520.3628FX-F 19x1.5820002220
24x1.518.322.1743FX-F 24x1.5820002230
30x1.520.224.0888FX-F 30x1.5820002240
37x1.522.226.01039FX-F 37x1.5820002250
48x1.525.029.01282FX-F 48x1.5820002260
3x2.510.013.8310FX-F 3x2.5820002280
4x2.510.013.8318FX-F 4x2.5820002290
5x2.510.914.7365FX-F 5x2.5820002300
7x2.511.915.7430FX-F 7x2.5820002310
10x2.514.117.9527FX-F 10x2.5820002320
12x2.515.319.1598FX-F 12x2.5820002330
14x2.516.320.1668FX-F 14x2.5820002340
19x2.518.722.5837FX-F 19x2.5820002350
24x2.520.724.51000FX-F 24x2.5820002360
30x2.522.926.71204FX-F 30x2.5820002370
37x2.525.329.11423FX-F 37x2.5820002380
48x2.528.933.11819FX-F 48x2.5820002390
2x410.013.8317FX-F 2x4820002400
3x410.314.1346FX-F 3x4820002410
4x411.315.1402FX-F 4x4820002420
5x412.316.1467FX-F 5x4820002430
7x413.517.3561FX-F 7x4820002440
10x416.019.8696FX-F 10x4820002450
12x417.421.2799FX-F 12x4820002460
14x418.622.4898FX-F 14x4820002470
19x421.325.11141FX-F 19x4820002480
24x423.727.51379FX-F 24x4820002490
30x426.330.31682FX-F 30x4820002500
37x429.433.62052FX-F 37x4820002510