series FX

0.6/1kV
Flexible Cu 1 up to 4mm²
Up to 48 Conductors
XLPE 90°C / PVC

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried.

Features

  • Temperature rating: 90ºC (operating),130ºC (overload) and 250ºC (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 2178-1 – IEC 60502-1

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Cross-linked polyethylene)

  • Sheath: PVC, fire-retardant; sunlight and oils resistant

  • Fire requirements: As per IEC 60332-1

  • Oils requirements: As per ICEA S 73-532

  • Outdoor requirements: As per UL 2556 (UV rays)

Flame retardant

Flame retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Tray cable

Tray cable

Identification

Standard
Sheath Conductors
Multiconductors alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Nominal cross-section sq mm² Electrical resistance at 20ºC in C.C Ohm/km Electrical resistance at 90ºC in C.A. Ohm/km Current-carrying capacity in free air. At 40°C as per IEC 364-5-523. Formations in perforated trays or ladder type. (Ampere)
2x 4x 7x 10x 19x 30x 48x
119.524.86--------------
1.513.316.96232016.111.511.510.48.1
2.57.9810.18312821.715.515.514.010.9
44.956.31433630.121.521.519.4--

As from seven-conductors, we’ve additionally applied the correction factor for more than three conductors the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x cross-section (mm²) External diameter mm Weight kg/km Code
2x18.283FX 0210
3x18.694FX 0310
4x19.3110FX 0410
5x110.0130FX 0510
7x110.8156FX 0710
10x113.6211FX 1010
12x114.0237FX 1210
14x114.7265FX 1410
19x116.2334FX 1910
24x118.8410FX 2410
30x119.9487FX 3010
37x121.4579FX 3710
48x124.4728FX 4810
2x1.58.798FX 0215
3x1.59.2114FX 0315
4x1.59.9134FX 0415
5x1.510.7159FX 0515
7x1.511.6194FX 0715
10x1.514.6262FX 1015
12x1.515.1297FX 1215
14x1.515.8334FX 1415
19x1.517.5426FX 1915
24x1.520.3526FX 2415
30x1.521.5630FX 3015
37x1.523.2754FX 3715
48x1.526.5953FX 4815
2x2.59.6127FX 0225
3x2.510.1151FX 0325
4x2.511.0181FX 0425
5x2.511.9216FX 0525
7x2.512.9269FX 0725
10x2.516.3361FX 1025
12x2.516.9414FX 1225
14x2.517.7470FX 1425
19x2.519.6607FX 1925
24x2.522.9754FX 2425
30x2.524.3912FX 3025
37x2.526.21099FX 3725
48x2.530.31413FX 4825
2x410.7169FX 0240
3x411.3205FX 0340
4x412.3249FX 0440
5x413.3300FX 0540
7x414.5380FX 0740
10x418.5509FX 1040
12x419.1589FX 1240
14x420.1673FX 1440
19x422.3878FX 1940
24x426.11097FX 2440
30x427.91349FX 3040
37x430.21633FX 3740