Marlew

series CX

600 Volt
Cu 14 up to 10 AWG
XHHW-2
UL 1277

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. Manufactured in compliance with the National Electrical Code ANSI/NFPA 70 of the US and the National Electrical Code NOM-001 SEDE, Mexico.

Features

  • Temperature rating: 90ºC (operating), 130ºC (overload), 250ºC (short circuit)

  • Voltage rating: 600V AC

  • Construction requirements: As per UL 1277

  • Conductor requirements: As per ASTM B8

  • Conductor: Annealed electrolytic copper conductor, class B stranding

  • Insulation: XLPE (Crosslinked polyethylene) type XHHW-2

  • Sheath: Flame retardant PVC

  • Fire requirements: As per UL 1685

  • Outdoors requirements: As per UL 2556 (UV rays)

  • NEC code (NFPA 70): Art. 336 TC –Art. 501 classified areas CL1 Div.2 y Cl2 Div.2

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

NEC cod

NEC cod

Tray cable

Tray cable

Identification

Standard
Sheath Conductors
Multiconductor alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version. Upon request, we can supply cables with different alternatives of identification, cable flexibility, or also including additional shield for suitable electromagnetic protection.

ELECTRICAL CHARACTERISTICS

Calibre AWG Electrical resistance at 20°C in C.C. (Ohm/km) Electrical resistance at 90°C in C.A. at 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x 48x
148.7911.21252017.512.512.511.38.8
125.547.06302421151513.510.5
103.484.4440322820201814

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x gauge AWG External diameter mm Weight kg/km Code Mat Number
2x149,0116CX 2X14820060600
3x149,5139CX 3X14820060610
4x1410,4168CX 4X14820060620
5x1411,4199CX 5X14820060630
7x1412,4256CX 7X14820060640
10x1416,3357CX 10X14820060650
12x1416,8411CX 12X14820060660
14x1418,0470CX 14X14820060670
16x1419,0527CX 16X14820060680
19x1420,0613CX 19X14820060690
21x1422,1721CX 21X14820060700
24x1424,1815CX 24X14820060710
27x1424,6896CX 27X14820060720
30x1425,8984CX 30X14820060730
32x1426,71045CX 32X14820060740
37x1427,81186CX 37X14820060750
48x1431,31500CX 48X14820060760
2x1210,0154CX 2X12820060770
3x1210,6188CX 3X12820060780
4x1211,6230CX 4X12820060790
5x1212,7274CX 5X12820060800
7x1214,6382CX 7X12820060810
10x1218,2495CX 10X12820060820
12x1218,8574CX 12X12820060830
14x1220,1660CX 14X12820060840
16x1222,3793CX 16X12820060850
19x1223,4921CX 19X12820060860
21x1224,71008CX 21X12820060870
24x1226,91144CX 24X12820060880
27x1227,51263CX 27X12820060890
30x1228,91390CX 30X12820060920