Marlew

LSZH series BZ

0.6/1kV
Flexible Cu 1.5 up to 300mm²
XLPE 90°C / LSZH
IRAM 62266

Variable frequency drive motor feed (VFD) in closed environments with a high concentration of people or in locations with equipment sensitive to exposure to corrosive gases. For Alternating Current (50/60Hz), for three-phase systems (380/190V) and systems with voltages up to 1kV. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried.

Features

  • Temperature rating: 90ºC (operating), 130ºC (overload), 250ºC (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 62266 – IEC 60502-1

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Crosslinked polyethylene)

  • Bedding: Double helical wrapping

  • Shield: Composed of a concentric conductor made of copper wires plus an anti-unwinding copper tape. The shield cross-section is indicated in the electrical characteristics table.

  • Sheath: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant) flame retardant, sunlight, and oil resistant

  • Flame propagation standard: As per IEC IEC 60332-1

  • Fire spread prevention standard: IEC 60332-3-24

  • Standard for halogen absence and corrosive gases: As per IEC 60754-1/2

  • Smoke transparency requirements: As per IEC 61034-1/2

  • Toxicity standard: As per NES 713 – CEI 20.37

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

  • Water behaviour requirements: Suitable AD7 (Occasional water submersion)

Electromagnetic interference protection

Electromagnetic interference protection

Fire-retardant

Fire-retardant

Halogen free

Halogen free

Low smoke

Low smoke

Flexible stranded conductors

Flexible stranded conductors

UV resistant

UV resistant

Identification

Standard
Sheath Conductors
3 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Nominal cross-section sq (mm²) Nominal cross-section Concentric conductor sq mm² Electrical resistance at 20°C in C.C.  Ohm/km Electrical resistance at 20°C in C.C. Concentric conductor Ohm/km Electrical resistance at 90°C en C.C. Ohm/km Electrical resistance at 90°C en C.C. Concentric conductor Ohm/km Inductive reactance at 50Hz (Ohm/Km) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523. Cables displayed in Cable Ladder or perforated tray. (Ampere) Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523. (Ampere)
1.5613.33.316.964.210.1002028
2.567.983.310.184.210.0932837
464.953.36.314.210.0883648
663.33.34.214.210.0834761
10101.911.912.442.440.0786583
16161.211.211.541.540.07586107
25160.781.210.991.540.075109141
35160.5541.2100.7071.540.073137168
50250.3860.7800.4930.990.073166199
70350.2720.5540.3480.7070.071213243
95500.2060.3860.2640.4930.070257293
120700.1610.2720.2070.3480.070299333
150700.1290.2720.1670.3480.070345373
185950.1060.2060.1380.2640.070394425
2401200.08010.1610.1060.2070.069465493
3001500.06410.1290.08600.1670.069537559

DIMENSIONS & WEIGHT

Cable Formation, N° Cond. x cross-section (mm²) Shield diameter (mm) External diameter mm Weight kg/km Code Mat Number
3 x 1.58.111.2227BZ 3X1.5+B6830151010
3 x 2.59.012.1260BZ 3X2.5+B6830151020
3 x 410.213.3310BZ 3X4+B6830151030
3 x 611.314.4370BZ 3X6+B6830151040
3 x 1013.416.5538BZ 3X10+B10830151050
3 x 1615.618.7751BZ 3X16+B16830151060
3 x 2519.222.31024BZ 3X25+B16830151070
3 x 3521.724.81303BZ 3X35+B16830151080
3 x 5026.329.51859BZ 3X50+B25830151090
3 x 7030.333.72531BZ 3X70+B35830151100
3 x 9533.4373259BZ 3X95+B50830151110
3 x 12037.541.34249BZ 3X120+B70830151120
3 x 15046.850.95309BZ 3X150+B70830151130
3 x 18550.855.36634BZ 3X185+B95830151140
3 x 24058.1638468BZ 3X240+B120830151150
3 x 30061.766.710337BZ 3X300+B150830151160

The tolerance for the reported diameters shall be between -5% and +8%.