LSZH series BX C

0.6/1kV
Flexible Cu 1.5 up to 300mm²
XLPE 90°C / LSZH
PE conductor

Variable frequency drive motor feed (VFD) in closed environments with a high concentration of people or in locations with equipment sensitive to exposure to corrosive gases. For Alternating Current (50/60Hz), for three-phase systems (380/190V) and systems with voltages up to 1kV. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried.

Features

  • Temperature rating: 90ºC (operating), 130ºC (overload), 250ºC (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 62266 – IEC 60502-1

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Crosslinked polyethylene)

  • Bedding: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant)

  • Shield: Copper tape (if necessary) with adequate overlap and 100% coverage. See the table for shield cross-section values

  • Sheath: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant) flame retardant, sunlight, and oil resistant

  • Fire requirements: As per IEC 60332-3-24

  • Standard for halogen absence and corrosive gases: As per IEC 60754-1/2

  • Smoke transparency requirements: As per IEC 61034-1/2

  • Toxicity standard: As per NES 713 – CEI 20.37

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

  • Water behaviour requirements: Suitable AD7 (Occasional water submersion)

Electromagnetic interference protection

Electromagnetic interference protection

Fire-retardant

Fire-retardant

Halogen free

Halogen free

Low smoke

Low smoke

Flexible stranded conductors

Flexible stranded conductors

UV resistant

UV resistant

Identification

Standard
Sheath Conductors
3 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Nominal cross-section sq (mm²) Nominal cross-section Concentric conductor sq mm Electrical resistance at 20°C in C.C.  Ohm/km Electrical resistance at 20°C in C.C. Concentric conductor Ohm/km Electrical resistance at 90°C en C.C. Ohm/km Electrical resistance at 90°C en C.C. Concentric conductor Ohm/km Inductive reactance at 50Hz (Ohm/Km) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523. Cables displayed in Cable Ladder or perforated tray. (Ampere) Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523. (Ampere)
1619.53.324.864.210.107----
1.5613.33.316.964.210.12028
2.567.983.310.184.210.0932837
464.953.36.314.210.0883648
663.33.34.214.210.0834761
10101.911.912.442.440.0786583
16161.211.211.541.540.07586107
25160.781.210.991.540.075109141
35160.5541.210.7071.540.073137168
50250.3860.780.4930.990.073166199
70350.2720.5540.3480.7070.071213243
95500.2060.3860.2640.4930.07257293
120700.1610.2720.2070.3480.07299333
150700.1290.2720.1670.3480.07345373
185950.1060.2060.1380.2640.07394425
2401200.08010.1610.1060.2070.069465493
3001500.06410.1290.0860.1670.069537559

DIMENSIONS & WEIGHT

Cable Formation, N° Cond. x cross-section (mm²) Diameter under shield mm External diameter mm Weight kg/km Code
3 x 19.013.3249BX 0310 C
3 x 1.59.013.3257BX 0315 C
3 x 2.59.313.7282BX 0325 C
3 x 410.314.7341BX 0340 C
3 x 611.716.1419BX 0360 C
3 x 1014.018.3620BX 3100 C
3 x 1616.020.4869BX 3160 C
3 x 2519.523.81,202BX 3250 C
3 x 3521.726.11,524BX 3350 C
3 x 5025.129.52,094BX 3500 C
3 x 7030.335.12,962BX 3700 C
3 x 9534.640.63,871BX 3950 C
3 x 12038.044.34,926BX 31200 C
3 x 15044.150.76,049BX 31500 C
3 x 18547.954.87,346BX 31850 C
3 x 24055.362.39,563BX 32400 C
3 x 30061.769.211,899BX 33000 C