Marlew

series BSR

0.6/1kV
XLPE 90°C / PVC
Includes PE conductor
Flexible CU 1.5 up to 150mm²

Power supply of submersible pumps used in potable-water wells under 40ºC, in flooded areas, to evacuate swimming pools, to filter or clean the water in tanks or similar sites. For Alternating Current (50/60Hz), for single-phase systems (220/110V), three-phase systems (380/190V) and systems with voltages up to 1kV. For Direct Current, used in systems with voltages up to 1.5kV

Features

  • Temperature ratings: 90°C (Operating) – 130°C (Overload) – 25 0°C (Short-Circuit)

  • Voltage rating: 600/1000 Volt A.C. – 1200 Volt A.C. (Max) – 1500 Volt D.C.

  • Construction requirements: IRAM 63007

  • Conductor requirements: IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Cross-Linked Polyethylene)

  • Assembly: Conductors gathered

  • Sheath: Flame retardant PVC

  • Fire requirements: As per IEC 60332-1

  • Outdoors requirements: As per UL 2556 (rayos UV)

  • Permanent immersion test in water: AD8

Flame retardant

Flame retardant

Flexible stranded conductors

Flexible stranded conductors

UV resistant

UV resistant

Industrial applications

Industrial applications

Submersible Pump

Submersible Pump

Diving up to 200 meters

Diving up to 200 meters

Identification

Standard
Sheath Conductors
1 Conductor
2 Conductors
3 Conductors whit PE
3 Conductors
4 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances and reactance

Nominal cross-section (mm²) Class 5. Electrical resistance in D.C. at 20°C (Ohm/km) Electrical resistance in C.C. at 90°C (Ohm/km) Inductive reactance at 50Hz (Ohm/Km)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) Multiconductor (4) 4 Conductors (5)
1.513.316.96------0.1180.126
2.57.9810.18------0.1090.117
44.956.31--------0.11
63.34.21--------0.103
101.912.44--------0.099
161.211.54--------0.094
250.780.990.1170.1610.103--0.094
350.5540.710.130.1560.098--0.091
500.3860.490.110.1530.095--0.09
700.2720.350.1040.1480.09--0.086
950.2060.260.1030.1470.088--0.086
1200.1610.210.1010.1440.086----
1500.1290.170.0990.1430.085----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) Calculation of Inductive reactance valid for two-conductor and three conductor cables. (5) Calculation of Inductive reactance valid for four-conductor cables.

Intensity of admissible currents

Nominal cross-section (mm²) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523.Single-conductors cable up to 16mm² in contact with each other, displayed in unperforated trays, remaining cross-sections, single-conductors displays and formations in cable ladder or perforated cable trays (Ampere) Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523 (Ampere)
Unipolar (1) Unipolar (2) Unipolar (3) Bipolar Multipolar Unipolar (1) Unipolar (2) Bipolar Multipolar
1.5------2320----3228
2.5------3128----4437
4--------36------48
6--------47------61
10--------65------83
16--------86------107
25122158117--109157168--141
35152196146--137188201--168
50187238179--166220235--199
70241305232--213271290--243
95295371283--257326349--293
120346432332----371397----
150401499384----415444----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other.

DIMENSIONS & WEIGHT

TrainingN° Conductors x section (mm²) External diametermm Weightkg/km Code Mat Number
1 x 2511,6296BSR 1X25830150510
1 x 3512,9396BSR 1X35830150520
1 x 5014,7540BSR 1X50830150530
1 x 7016,6741BSR 1X70830150540
1 x 9518,4950BSR 1X95830150550
1 x 12020,31206BSR 1X120830150560
1 x 15023,31510BSR 1X150830150570
2 x 1.59,5113BSR 2X1.5830150890
2 x 2.510,4143BSR 2X2.5830150891
3 x 1.510,1130BSR 3X1.5830150892
3 x 2.511,0168BSR 3X2.5830150893
3 x 412,4229BSR 3X4830150894
3 x 613,5299BSR 3X6830150895
3 x 1016,7482BSR 3X10830150896
3 x 1620,8772BSR 3X16830150897
3 x 2524,81138BSR 3X25830150898
3 x 3527,31474BSR 3X35830150899
3 x 5032,02058BSR 3X50830150900
3 x 7035,82755BSR 3X70830150901
3 x 9540,03526BSR 3X95830150902
3 x 12044,24457BSR 3X120830150903
3 x 15050,75625BSR 3X150830150904
2 x 1.5 + 1 x 1.510,1130BSR 2X1.5+PE1.5830150905
2 x 2.5 + 1 x 2.511,0168BSR 2X2.5+PE2.5830150906
2 x 4 + 1 x 412,4229BSR 2X4+PE4830150907
2 x 6 + 1 x 613,5299BSR 2X6+PE6830150908
2 x 10 + 1 x 1016,7482BSR 2X10+PE10830150909
2 x 16 + 1 x 1620,8772BSR 2X16+PE16830150910
2 x 25 + 1 x 2524,81138BSR 2X25+PE25830150911
2 x 35 + 1 x 3527,31474BSR 2X35+PE35830150912
2 x 50 + 1 x 5032,02058BSR 2X50+PE50830150913
2 x 70 +1 x 7035,82755BSR 2X70+PE70830150914
2 x 95 + 1 x 9540,03526BSR 2X95+PE95830150915
2 x 120 1 x 12044,24457BSR 2X120+PE120830150916
2 x 150 + 1 x 15050,75625BSR 2X150+PE150830150917
3 x 1.5 + 1 x 1.511,0154BSR 3X1.5+PE1.5830150918
3 x 2.5 + 1 x 2.512,0202BSR 3X2.5+PE2.5830150919
3 x 4 + 1 x 413,5277BSR 3X4+PE4830150920
3 x 6 + 1 x 614,8365BSR 3X6+PE6830150921
3 x 10 + 1 x 1018,4594BSR 3X10+PE10830150922
3 x 16 + 1 x 1622,9954BSR 3X16+PE16830150923
3 x 25 + 1 x 2527,11399BSR 3X25+PE25830150924
3 x 35 + 1 x 3530,11840BSR 3X35+PE35830150925
3 x 50 + 1 x 5035,32569BSR 3X50+PE50830150926
3 x 70 +1 x 7039,53457BSR 3X70+PE70830150927
3 x 95 + 1 x 9544,84495BSR 3X95+PE95830150928
3 x 120 1 x 12048,75530BSR 3X120+PE120830150929
3 x 150 + 1 x 15059,17205BSR 3X150+PE150830150930