Marlew

Clad series BX-F

0.6/1kV
Flexible Cu 1.5 up to 300mm²
XLPE 90°C / PVC
IRAM 2178-1

Variable frequency drive motor feed. (VFD) For Alternating Current (50/60Hz), for three-phase systems (380/190V) and systems with voltages up to 1kV. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Maximum temperature: 90°C maximum service – 130°C overload – 250°C short-circuit

  • Rated voltage: 600/1000 Volt AC – 1200 Volt AC (Maximum) – 1500 Volt DC

  • Construction standard: IRAM 2178-1 – IEC 60502-1

  • Conductor standard: IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper, flexible class 5 stranding

  • Insulation: XLPE (Cross-linked polyethylene)

  • Bedding: Extruded PVC

  • Screen: Consisting of copper wires plus a copper tape with 100% coverage. The screen cross-section is indicated in the electrical characteristics table

  • Inner sheath: PVC, fire retardant

  • Armour: Double helical galvanized (zinc-coated) steel tape

  • Sheath: PVC, fire retardant

  • Flame non-propagation standard: IEC 60332-1

  • Fire non-propagation standard: IEC 60332-3-24

  • Weathering standard: UL 2556 (UV rays)

Electromagnetic interference protection

Electromagnetic interference protection

Fire-retardant

Fire-retardant

Flexible stranded conductors

Flexible stranded conductors

UV resistant

UV resistant

Sequentially marked

Sequentially marked

Industrial applications

Industrial applications

Identification

Standard
Sheath Conductors
3 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Nominal cross-section (mm²) Concentric conductor nominal cross-section (mm²) DC electrical resistance at 20°C (Ohm/km) Concentric conductor DC electrical resistance at 20°C (Ohm/km) DC electrical resistance at 90°C (Ohm/km) Concentric conductor DC electrical resistance at 90°C (Ohm/km) Inductive reactance at 50Hz. (Ohm/Km) Current rating, cables in air. At 40°C according to IEC 364-5-523. Laid on perforated or ladder-type trays. (Amper) Current rating, cables directly buried. At 25°C ground temperature and soil thermal resistivity of 1 k.m/W. according to IEC 364-5-523. (Amper)
2.567.983.310.184.210.0932837
464.953.36.314.210.0883648
663.33.34.214.210.0834761
10101.911.912.442.440.0786583
16161.211.211.541.540.07586107
25160.781.210.991.540.075109141
35160.5541.2100.7071.540.073137168
50250.3860.7800.4930.990.073166199
70350.2720.5540.3480.7070.071213243
95500.2060.3860.2640.4930.070257293
120700.1610.2720.2070.3480.070299333
150700.1290.2720.1670.3480.070345373
185950.1060.2060.1380.2640.070394425
2401200.08010.1610.1060.2070.069465493
3001500.06410.1290.08600.1670.069537559

DIMENSIONS & WEIGHT

Cable Formation, N° Cond. x cross-section (mm²) Shield diameter (mm) Diameter below armour mm External diameter mm Weight kg/km Code Mat Number
3 x 2.510.61316.8453BX-F 3X2.5+B6830150030
3 x 411.714.117.9520BX-F 3X4+B6830150040
3 x 612.915.319.1610BX-F 3X6+B6830150050
3 x 1015.017.421.2828BX-F 3X10+B10830150060
3 x 1617.119.523.31105BX-F 3X16+B16830150070
3 x 2520.723.126.91470BX-F 3X25+B16830150080
3 x 3522.925.329.11797BX-F 3X35+B16830150090
3 x 5026.729.133.12477BX-F 3X50+B25830150100
3 x 7032.935.339.73437BX-F 3X70+B35830150110
3 x 9537.239.645.44762BX-F 3X95+B50830150120
3 x 12040.44349.25970BX-F 3X120+B70830150130
3 x 15047.350.156.57429BX-F 3X150+B70830150140
3 x 18552.355.361.98948BX-F 3X185+B95830150150
3 x 24058.261.468.411282BX-F 3X240+B120830150160
3 x 30065.568.976.313702BX-F 3X300+B150830150170