Marlew

series BX 3+3

0.6/1kV
Flexible CU 2.5 up to 300mm²
XLPE 90°C / PVC
3 PE Conductors

Variable frequency drive motor feed. (VFD) For Alternating Current (50/60Hz), for three-phase systems (380/190V) and systems with voltages up to 1kV. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried.

Features

  • Maximum temperature: 90°C maximum service – 130°C overload – 250°C short-circuit

  • Rated voltage: 600/1000 Volt AC – 1200 Volt AC (Maximum) – 1500 Volt DC

  • Construction standard: IRAM 2178-1 – IEC 60502-1

  • Conductor standard: IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper, flexible class 5 stranding

  • Insulation: XLPE (Cross-linked polyethylene)

  • Core assembly: 3 phases + 3 protective earth (PE) conductors laid in the interstices between the phases, forming a symmetrical cable

  • Bedding: Extruded PVC

  • Screen: Consisting of copper wires plus a copper tape with 100% coverage. The screen cross-section is indicated in the electrical characteristics table

  • Sheath: PVC, fire retardant

  • Flame non-propagation standard: IEC 60332-1

  • Fire non-propagation standard: IEC 60332-3-24

  • Weathering standard: UL 2556 (UV rays)

Electromagnetic interference protection

Electromagnetic interference protection

Flame retardant

Flame retardant

Flexible stranded conductors

Flexible stranded conductors

UV resistant

UV resistant

Sequentially marked

Sequentially marked

Industrial applications

Industrial applications

Identification

Standard
Sheath Conductors
3 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Nominal cross-section (mm²) Nominal cross-section PE earthing conductors (mm²) Concentric conductor nominal cross-section (mm²) DC electrical resistance at 20°C (Ohm/km) DC electrical resistance at 20°C of the PE earthing conductor (Ohm/km) DC electrical resistance at 90°C (Ohm/km) DC electrical resistance at 90°C of the PE earthing conductor (Ohm/km) Inductive reactance at 50Hz. (Ohm/Km) Current rating, cables in air. At 40°C according to IEC 364-5-523. Laid on perforated or ladder-type trays. (Amper) Current rating, cables directly buried. At 25°C ground temperature and soil thermal resistivity of 1 k.m/W. according to IEC 364-5-523. (Amper)
2.510.257.9819.510.1824.860.0932837
41.50.44.9513.36.3116.960.0883648
62.50.63.37.984.2110.180.0834761
10411.914.952.446.310.0786583
1661.61.213.31.544.210.07586107
2562.50.783.30.994.210.075109141
3563.50.5543.30.7074.210.073137168
501050.3861.910.4932.440.073166199
701670.2721.210.3481.540.071213243
95169.50.2061.210.2641.540.070257293
12025120.1610.780.2070.990.070299333
15025150.1290.780.1670.990.070345373
1853518.50.1060.5540.1380.7070.070394425
24050240.08010.3860.1060.4930.069465493
30050300.06410.3860.08600.4930.069537559

DIMENSIONS & WEIGHT

Cable formation N° Cond. x cross-section (mm²) Shield diameter (mm) External diameter mm Weight kg/km Code Mat Number
3x2.5+3x111.714.8288BX 3X2.5+3PE1+B10%830044180
3x4+3x1.512.815.9355BX 3X4+3PE1.5+B10%830044190
3x6+3x2.514.417.5457BX 3X6+3PE2.5+B10%830044200
3x10+3x416.519.6643BX 3X10+3PE4+B10%830044210
3x16+3x618.821.9876BX 3X16+3PE6+B10%830044220
3x25+3x620.823.91153BX 3X25+3PE6+B10%830044230
3x35+3x622.025.11407BX 3X35+3PE6+B10%830044240
3x50+3x1026.129.22019BX 3X50+3PE10+B10%830044250
3x70+3x1631.134.32834BX 3X70+3PE16+B10%830044260
3x95+3x1635.338.73478BX 3X95+3PE16+B10%830044270
3x120+3x2538.642.44564BX 3X120+3PE25+B10%830044280
3x150+3x2546.450.45687BX 3X150+3PE25+B10%830044290
3x185+3x3551.555.86944BX 3X185+3PE35+B10%830044300
3x240+3x5057.161.89097BX 3X240+3PE50+B10%830044310
3x300+3x5064.569.410732BX 3X300+3PE50+B10%830044320