series SHD-GCThis type of cable is required for extra-heavy duty industrial use. They are power cables for voltage up to 2000V, reinforced portable, for use in mining developments for heavy mobile equipment such as cables drag, shovels, drills and power feeders. In oil fields it is used for feeding mobile drilling equipment, and in general for mobile outdoor installations with vertical and horizontal movement. It can withstand, while fixed or in movement, all types of efforts: traction, torsion, and flexion; caused by standard cable winding equipment. It counts with plastic materials which provide suitable protection against chemical products, harsh environment, tear and impacts. Additionally, these materials do not release halogen gases in the event of a fire. Suitable for applications where grounding conductors (G) and ground check conductors (GC) are needed The cable has individual shielding on each phase conductor.
| Flexible armored | |
|---|---|
| Sheat | ![]() |
| Conductors | ![]() ![]() ![]() |
| Ground conductor | SIN AISLAR |
| Ground check conductors | ![]() |
The information supplied corresponds to the standard version, upon request these cables can be supplied with untinned copper conductors or with another color of cover.
| Phase conductor gauge (AWG/MCM) | Protective conductor gauge (AWG) | Check conductor gauge (AWG) | Electrical resistance in DC at 20°C (*) | Admissible intensity in air (**) | External diameter | Weight approx. | Radius of curvature | Tensile stress | Marlew Code |
|---|---|---|---|---|---|---|---|---|---|
| 3x | 2x | 1x | ohm/km | Amper | mm | kg/km | mm | daN | |
| 12 | 12 | 14 | 6.10 | -- | 23 | 639 | 138 | 93 | SHD-GC-2kV 3x12+2G12+GC14 |
| 10 | 12 | 12 | 3.86 | -- | 24 | 720 | 144 | 129 | SHD-GC-2kV 3x10+2G12+GC12 |
| 8 | 12 | 12 | 2.46 | 59 | 27 | 907 | 162 | 175 | SHD-GC-2kV 3x8+2G12+GC12 |
| 6 | 10 | 10 | 1.50 | 79 | 32.8 | 1335 | 197 | 278 | SHD-GC-2kV 3x6+2G10+GC10 |
| 4 | 8 | 10 | 0.94 | 104 | 35.6 | 1717 | 214 | 427 | SHD-GC-2kV 3x4+2G8+GC10 |
| 3 | 7 | 10 | 0.74 | 120 | 38.4 | 2048 | 230 | 532 | SHD-GC-2kV 3x3+2G7+GC10 |
| 2 | 6 | 10 | 0.59 | 138 | 40.4 | 2343 | 242 | 663.1 | SHD-GC-2kV 3x2+2G6+GC10 |
| 1 | 5 | 8 | 0.472 | 161 | 44.7 | 2952 | 268 | 846 | SHD-GC-2kV 3x1+2G5+GC8 |
| 1/0 | 4 | 8 | 0.376 | 186 | 47.2 | 3473 | 283 | 1055 | SHD-GC-2kV 3x1/0+2G4+GC8 |
| 2/0 | 3 | 8 | 0.299 | 215 | 50.8 | 4182 | 305 | 1320 | SHD-GC-2kV 3x2/0+2G3+GC8 |
| 3/0 | 2 | 8 | 0.237 | 249 | 54.1 | 4899 | 325 | 1653 | SHD-GC-2kV 3x3/0+2G2+GC8 |
| 4/0 | 1 | 8 | 0.188 | 287 | 58.7 | 5988 | 352 | 2071 | SHD-GC-2kV 3x4/0+2G1+GC8 |
| 250 | 1/0 | 8 | 0.161 | 320 | 63.8 | 6894 | 383 | 2482 | SHD-GC-2kV 3x250+2G1/0+GC8 |
| 300 | 1/0 | 8 | 0.134 | 357 | 68.1 | 7774 | 409 | 2857 | SHD-GC-2kV 3x300+2G1/0+GC8 |