series G-GC-LIn oil fields it is used for feeding mobile drilling equipment, and in general for mobile outdoor installations with vertical and horizontal movement. It can withstand, while fixed or in movement, all types of efforts: traction, torsion, and flexion; caused by standard cable winding equipment. It counts with plastic materials which provide suitable protection against chemical products, harsh environment, tear and impacts. Additionally, these materials do not release halogen gases in the event of a fire. Suitable for applications where grounding conductors (G) and ground check conductors (GC) are needed This type of cable is required for extra-heavy duty industrial use. They are portable, reinforced power cables for use in mining developments for heavy mobile equipment such as tow cables, shovels, drills and power feeders.
| Flexible armored | |
|---|---|
| Sheat | ![]() |
| Conductors | ![]() ![]() ![]() |
| Ground conductor | SIN AISLAR |
| Ground check conductors | ![]() |
The information supplied corresponds to the standard version; upon request these cables can be supplied with another color cover.
| Phase conductor gauge (AWG/MCM) | Protective conductor gauge (AWG) | Check conductor gauge (AWG) | Electrical resistance in DC at 20°C (*) | Admissible intensity in air (**) | External diameter | Weight approx. | Radio de curvatura | Tensile stress | Marlew Code |
|---|---|---|---|---|---|---|---|---|---|
| 3x | 2x | 1x | ohm/km | Amper | mm | kg/km | mm | daN | |
| 8 | 10 | 10 | 2.30 | 59 | 24.6 | 805 | 148 | 204 | G-GC-L-2kV 3x8+2G10+GC10 |
| 6 | 10 | 10 | 1.44 | 79 | 26.7 | 1012 | 160 | 278 | G-GC-L-2kV 3x6+2G10+GC10 |
| 4 | 8 | 10 | 0.906 | 104 | 30.2 | 1415 | 181 | 427 | G-GC-L-2kV 3x4+2G8+GC10 |
| 3 | 8 | 10 | 0.720 | 120 | 31.8 | 1606 | 191 | 510 | G-GC-L-2kV 3x3+2G8+GC10 |
| 2 | 7 | 10 | 0.572 | 138 | 34 | 1882 | 204 | 636 | G-GC-L-2kV 3x2+2G7+GC10 |
| 1 | 6 | 8 | 0.451 | 161 | 38.4 | 2388 | 230 | 811 | G-GC-L-2kV 3x1+2G6+GC8 |
| 1/0 | 5 | 8 | 0.362 | 186 | 41.9 | 2934 | 251 | 1012 | G-GC-L-2kV 3x1/0+2G5+GC8 |
| 2/0 | 4 | 8 | 0.287 | 215 | 44.5 | 3505 | 267 | 1264 | G-GC-L-2kV 3x2/0+2G4+GC8 |
| 3/0 | 3 | 8 | 0.228 | 249 | 48 | 4237 | 288 | 1584 | G-GC-L-2kV 3x3/0+2G3+GC8 |
| 4/0 | 2 | 8 | 0.181 | 287 | 51.8 | 5109 | 311 | 1983 | G-GC-L-2kV 3x4/0+2G2+GC8 |
| 250 | 2 | 8 | 0.154 | 320 | 60.7 | 6160 | 364 | 2283 | G-GC-L-2kV 3x250+2G2+GC8 |
| 300 | 1 | 8 | 0.129 | 357 | 65 | 7155 | 390 | 2746 | G-GC-L-2kV 3x300+2G1+GC8 |
| 350 | 1/0 | 8 | 0.110 | 394 | 68.1 | 8237 | 409 | 3232 | G-GC-L-2kV 3x350+2G1/0+GC8 |
| 400 | 1/0 | 8 | 0.096 | 430 | 71.6 | 9037 | 430 | 3622 | G-GC-L-2kV 3x400+2G1/0+GC8 |
| 450 | 2/0 | 8 | 0.086 | 460 | 74.7 | 10231 | 448 | 4136 | G-GC-L-2kV 3x450+2G2/0+GC8 |
| 500 | 2/0 | 8 | 0.077 | 487 | 77 | 10829 | 462 | 4511 | G-GC-L-2kV 3x500+2G2/0+GC8 |
(*) The electrical resistance reported corresponds only to the phase conductors. (**)Table H-1 of ICEA S 75-381 standard, maximum service temperature at 90ºC and ambient temperature of 40ºC